Emergency Power Supply Unit

Emergency Power Supply Unit

Emergency Power Supply Unit

VX-2000DS AMQ

The VX-2000DS Emergency Power Supply Unit supplies DC backup power to each component in the VM-3000 system. It keeps the 2 × 12 V sealed lead batteries charged, compensating for the temperature of the battery charging voltage. When AC Power is disrupted, the VX-2000DS is automatically switched to the backup batteries.


VM-3000 TOA-Mass_Notification_Systems_Cookbook
VM-3000 Airport Application video clip
VM-3000 Airport Application
VM-3240 Setting Software Instructions


Power Source 120 V AC, 60 Hz
Power Consumption 240 W max.
Applicable Battery Panasonic LC-X/LC-P Series (12 V x 2)
Charging Method Trickle charging
Charging Current 5 A max.
Charging Output Voltage 27.3 V  ±0.3 V (at 25 °C)
Temperature correction coefficient: -40 mV/°C)
Power Supply Input 6, M4 screw terminal, distance between barriers: 11mm
DC Power Output Number of connectable equipment: Up to 3 VM-3240 AMQ, M4 screw terminal, distance between barriers: 11mm 
Control Connector RJ45 female connector for connecting the VM-3000 system
Twisted-pair straight cable (TIA/EIA-568A standard)
Type of control signal: Battery check, AC power status, DC power status, charging circuit failure, and battery failure 
Battery Connection 1 pair of positive and negative terminals
Applicable cable diameter: AWG 6 - AWG 0 (AWG 1/0) (Line resistance within 4 mΩ/total)
Cross sectional area: 16 - 50 ㎟
Operating Temperature 0 to +40°C (32 to 104°F)
Finish Panel: Surface-treated steel plate, black (30% gloss), paint
Dimensions 482 (W) x 88.4 (H) x 377.6 (D) mm (18.98" x 3.5" x 13.29")
Weight 10.5kg (23.15 lb)
Accessories Rack mounting screw (5x12) x 4, Fiber washer x 4, Blade fuse (40A) x 3, Fuse (T6.3 A L) x 1, Insulating sheet x 1, Thermal insulating sheet x 1, Power cable (2 m) x 1

Fuse ratings Blade fuse (40 A), Blasde fuse (7.5 A), Fuse (7.5 A)
Maximum output current draw from the battery 43.5 A
Maximum internal resistance of the battery and its associated circuitry, Ri max 50 mΩ
Recommended cable parameter for DS-SF Link Twisted-pair straight cable (TIA/EIA-568A standard)